Darfon

H100 Energy Storage System

Model Number: H100
The Darfon H100 is the ideal energy storage solution for residential and small commercial systems that require backup only a few times a year. It integrates lead acid AGM batteries, the H5000 hybrid inverter and charge controller into an industrial racking enclosure, so it is easy and fast to install. You just roll it in, install the batteries, connect the wires and then drive away. The H100 can be installed with up to 20kWh batteries, and since it uses AGM batteries, it is cost effective and low maintenance.
 
Battery Specifications - Deka Unigy I 12AVR100ET
Battery Nominal Voltage 48V (4 x 12V)
Battery Type Valve regulated lead acid with AGM
Design Life 10 years in float applications at 25°C (77°F)
Cells/Voltage Per Module 6 cells/12V
Capacity @ 25°C (77°F) 96Ah @ 8hr-rate to 1.75V/cell
Weight 34kg (75lb)
Container/Cover Flame-retardant, polypropylene, UL 94 V-0/>28% L.O.I.
Float Voltage 2.27V/cell ± 0.01V/cell
Max. Charge Current 30A
Peak Discharge Current 800A in 5 seconds
Terminal Type / Location Inserted post, 1/4” × 20 brass insert / Front
Dimensions (W x H x D) 113 x 257 x 512mm (4.4 x 10.1 x 20.2in)
Positive Plate Pure lead, low-calcium, high-tin alloy
Negative Plate Lead calcium alloy
Safety Vent Low positive pressure, self-sealing w/flame arrestor
Operating Temperature 10 to 40.5°C (50 to 105°F)
 
Battery Array Options
No. of Modules Capacity Total Weight
8 192Ah (9.2kWh) 272kg (600lb)
12 288Ah (13.8kWh) 408kg (899lb)
16 (default) 384Ah (18.4kWh) 544kg (1199lb)
 
Enclosure Specifications
Weight (w/o Batteries) 140kg (308lb)
Dimensions (W x D x H) 556 x 902x 1768mm (21.9 x 35.5 x 69.6in)
Protection Rating NEMA 1/IP20
Operating Temperature -10 to 60°C (14 to 140°F), power derated > 40°C/104°F
Safety Compliance UL 1741, IEEE 1547, FCC Part 15 Class B
 
H5000 Specifications
SOLAR DC INPUT
Max Power 6500W
Operation/MPPT Voltage Range 120 to 500VDC / 250 to 430VDC
Min Start Voltage 150 VDC
Max Input Current 13A / 13A (Two String Input)
EFFICIENCY
Peak PV to Grid 96%
CEC weighted PV to Grid 95.5%
INVERTER AC OUTPUT
Continuous Output Power @ 25°C 5000W
Overload 40sec/5sec/1sec @ 25°C 5500W/6500W/7500W
Rated Output Current (RMS) 21A (@120V and 240V)
Output Frequency (Auto Sensing) 50/60 Hz
Output Voltage L-N: 120V ± 3%; L-L: 240V ± 3%
AC INPUT FROM GRID
Automatic Transfer Relay Rating 33A
Typical Transfer Time 20ms
AC Input Voltage Range L-L: 180 to 280V (240V Nominal)
AC input Frequency Range 55 to 65 Hz
AC OUTPUT TO GRID
Grid Feed-In Current Range 0 to 24A (@240V)
Grid Feed-In Voltage Range L-L: 211 to 264V ± 3.0V
Grid Feed-In Frequency Range 59.4 to 60.4Hz ± 0.05Hz
DC BATTERY CHARGER
Max Charge Current 60A
Max Discharge Current 150A
DC Voltage Range 42 to 60V (48V Nominal)
*All specifications are subject to change without notice.
H5000 Certifications
H5000/H5001 Application Software
Back to Top